Surge Protective Device FV30C/3+NPE S

Item No: FV30C/3+NPE-xxx S
-Class II / Type 2 surge protective devices.
-Consisting of a base part and 3 MOV + 1GDT plug-in protection modules.
-For using in the lightning protection zones concept at boundary 1-2.
-The core parts are metal oxide vristor components with high discharge capacity.
-Low residual voltage and quick response
-Reliable control thanks to Thermo Dynamic Control disconnector.
-With remote signaling contact for control device.
-Fault indication via red mark in the inspection window.
-Protection mode: L1, L2, L3-N, N-PE.

Product Description

1.Coding system


2.Dimension and circuit of surge protective device FV30C/3+NPE-xxx S


3.Electrical parameters of surge protective device FV30C/3+NPE-xxx S

Model No. FV30C/3+NPE-
150S
FV30C/3+NPE-
275S
FV30C/3+NPE-
320S
Rated Voltage UN VAC 110/220 230/400 230/400
Max. continuous. operating voltage L-N UC VAC 150 275 320
Max. continuous. operating voltage N-PE UC VAC 255 255 255
Nominal discharge current(8/20μs) In kA 30 30 30
Max. discharge current (8/20μs) Imax kA 60 60 60
Voltage protection level (at In) Up kV ≤0.9 ≤1.5 ≤1.8
Voltage protection level (at In) Up kV ≤1.5 ≤1.5 ≤1.5
Response time tA ns <25 <25 <25
Recommended back-up fuse A 125 125 125
Protection mode L1, L2, L3-N, N-PE
I/O Connections By screw terminal:10-35mm2; By connection bus
Mounting Symmetrical rail(EN50022/DIN46277-3)
Operation temperature range -40℃~+85℃
Degree of protection IP20
Housing material UL94V0
Disconnection indicator Mechanical indicator (Green: ok, Red: replace)
Remote control contact Optional

4.Installation of surge protective device FV30C/3+NPE-xxx S