DC 3 poles 1000V type 1+2 surge protection with 18mm width
-DC surge protective devicespecially used for photovoltaic system less than 1000Vdc.
-The core parts are metal oxide varistor components with high discharge capacity.
-With Reliable control thanks to Thermo Dynamic Control disconnector.
-With remote signaling contact for control device.
-Fault indication via red mark in the inspection window.
Product Description

2. Dimension and Circuit of type 1+2 1000Vdc surge protection device

3. Type 1+2 1000Vdc surge protective device electrical parameters
|
Model. No. |
FV30B+C/3-1000PV |
|
SPD protection conforms to EN50539-11/IEC61643-31 |
Type 1+2 |
|
SPD installation type conforms to EN50539-11/IEC61643-31 |
ClassI+II |
|
Protection level conforms to DIN VDE0675-6 |
B+C |
|
Type of Network |
Photovoltaic systemsDC side |
|
Protectionmode |
(+/-)-PE, (-/+)-PE |
|
Nominal Voltage UN |
1000 Vdc |
|
Maximum continuous operating voltage for PV application UCPV |
1200 Vdc |
|
Continuous operating current ICPV |
<20 µA |
|
Residual current IPE |
≤20 µA dc ≤500 µA ac |
|
Standby power consumption PC |
≤25 mVA |
|
Maximum discharge current (8/20μs) Imax |
50 kA |
|
Nominal discharge current (8/20μs) In |
25 kA |
|
Impuse discharge current (10/350μs) Iimp |
5 kA |
|
Voltage protection level Up |
≤3.8 kV |
|
Isolation resistance Risol |
>1000 MΩ |
|
Response time tA |
≤25 ns |
|
Remote control contact |
YES |
|
Disconnection indicator |
Mechanical indicator (Green: OK, Red: Replace) |
|
Minimum area of connecting cable |
6mm2 |
|
Maximum area of connecting cable |
35mm2 |
|
Installation location |
Inside |
|
Mounting type |
35mm DIN rail acc. to EN 60715 |
|
Color |
Gray |
|
Degree of protection |
IP20 |
|
Housing material |
UL94V-0 |
|
Ambient temperature |
-40°C ~+80°C |
|
Altitude |
≤2000 m (amsl (above mean sea level)) |
|
Permissible humidity |
30%~90% |
4.Type 1+2 1000Vdc surge protective device installation