DC surge arresters FV20C/2-1000 PV
Item No: FV20C/2-1000 PV
-DC surge arresters specially used for photovoltaic solar panelsystem 1000Vdc.
-The core parts are metal oxide vristor components with high discharge capacity.
-With Reliable control thanks to Thermo Dynamic Control disconnector.
-Without remote signaling contact for control device.
-Fault indication via red mark in the inspection window.
Product Description
1. Coding system

2.Dimension and circuit of DC surge arresters (solar panel lightning protection) FV20C/2-1000PV

3.Electrical parameters of DC surge arresters (solar panel lightning protection) FV20C/2-1000PV
Hot Tags:DC surge arresters, DC surge arresters manufacturer,China DC surge arresters,
DC surge arresters supplier
4.Installation of DC surge arresters (solar panel lightning protection) FV20C/2-1000PV


2.Dimension and circuit of DC surge arresters (solar panel lightning protection) FV20C/2-1000PV

3.Electrical parameters of DC surge arresters (solar panel lightning protection) FV20C/2-1000PV
| Model No. | FV20C/2-1000PV | ||||
| Nominal voltage | Un | VDC | 1000 | ||
| Max.continuous d.c. voltage[(L+/L-)->PE]/ [L+->L-] | Uc pv | VDC | 1060 | ||
| Nominal discharge current(8/20μs) | In | kA | 20 | ||
| Max. discharge current (8/20μs) | Imax | kA | 40 | ||
| Voltage protection level (at In) | Up | kA | ≤3.6 | ||
| Response time | tA | ns | <25 | ||
| I/O Connections | By screw terminal:10-35mm2; By connection bus | ||||
| Mounting | Symmetrical rail(EN50022/DIN46277-3) | ||||
| Operation temperature range | -40℃~+85℃ | ||||
| Degree of protection | IP20 | ||||
| Housing material | UL94V0 | ||||
| Disconnection indicator | Mechanical indicator | ||||
| Remote control contact | Without | ||||
Hot Tags:DC surge arresters, DC surge arresters manufacturer,China DC surge arresters,
DC surge arresters supplier
4.Installation of DC surge arresters (solar panel lightning protection) FV20C/2-1000PV



English