New surge arrester type 1+2 Iimp 12.5kA
Item No: FVB12.5B+C/1- xxx (S)
1.Special design for saving installation space--- width 18mm/pole.
2.High discharge current--- Iimp 12.5kA per pole.
3.Indication window for clear display of SPD status--- each pole with one indication window.
4.Remote controlling function -for your option.
5.Pluggable module--- convenient for maintenance.
6. Protection mode --- L/N-PE
2.High discharge current--- Iimp 12.5kA per pole.
3.Indication window for clear display of SPD status--- each pole with one indication window.
4.Remote controlling function -for your option.
5.Pluggable module--- convenient for maintenance.
6. Protection mode --- L/N-PE
Product Description
8/20us 80kA test vedio, FVB12.5B+C/1-275S please click here.
1.Coding system
2.Dimension and circuit of FVB12.5B+C/1-xxx S
3.Electrical parameters of FVB12.5B+C/1-xxx S
4.Installation of FVB12.5B+C/1-xxx S
1.Coding system
2.Dimension and circuit of FVB12.5B+C/1-xxx S
3.Electrical parameters of FVB12.5B+C/1-xxx S
Model No. | FVB12.5B+C/1- 150 (S) |
FVB12.5B+C/1- 275 (S) |
||||
Rated Voltage | UN | VAC | 110 | 230 | ||
Max. continuous. operating voltage | UC | VAC | 150 | 275 | ||
Nominal discharge current(8/20μs) Max. discharge current(8/20μs) |
In Imax |
kA kA |
40 80 |
40 80 |
||
Iimpulse discharge current (10/350μs) | Iimp | kA | 12.5 | 12.5 | ||
Voltage protection level (at 20kA) Voltage protection level (at 40kA) |
Up Up |
kV kV |
≤0.7 ≤1.0 |
≤1.2 ≤1.7 |
||
Response time | tA | ns | <25 | <25 | ||
Recommended back-up fuse | A | 160 | 160 | |||
I/O Connections | By screw terminal:10-35mm2; By connection bus | |||||
Mounting | Symmetrical rail(EN50022/DIN46277-3) | |||||
Operation temperature range | -40℃~+85℃ | |||||
Degree of protection | IP20 | |||||
Housing material | UL94V0 | |||||
Disconnection indicator | Mechanical indicator | |||||
Remote control contact | Optional |
4.Installation of FVB12.5B+C/1-xxx S