RS485 data surge arrester 30Vdc
Item No: FS-DR-30/7.0
- Din rail RS485 datasurge arresters are applied to control signal double wire circuit in LPZ0 to LPZ3, e.g. 4~20mA circuit, RS485 circuit, RS422 circuit, gas detector, car-park system, CCTV remote monitor, remote control circuits.
- Common and difference surge protection mode, excellent performance.
- The pluggable module allows a fast replacement in case of fail.
- The grounding is realized through an earthing-clip on the DIN-Rail and / or earthing – clamp.
- No limiting in operating current due to parallel connecting method.
- Mounting on 35mm Rail, small space.
-Un 30Vdc, Uc 34.8Vdc
-Un 30Vdc, Uc 34.8Vdc
Product Description
1.Dimension and circuit diagram of RS485 data surge arrester FS-DR-30/7.0
2.Electrical parameters of RS485 data surge arrester FS-DR-30/7.0
2.Electrical parameters of RS485 data surge arrester FS-DR-30/7.0
Rated voltage |
Un |
30 V |
Max. cont. operating DC voltage |
Uc |
34.8 V |
Max. cont. operating AC voltage |
Uc |
24.5 V |
Rated current |
|
|
Nominal discharge current (8/20μs) |
In |
5 kA |
Max. discharge current (8/20μs) |
Imax |
10 kA |
Voltage protection level L/L(limp D1) |
Up |
≤ 130 V |
Voltage protection level L/PE (limp D1) |
Up |
≤ 80 V |
Each line sereis resistance |
1.8 Ohm |
|
Band width L/L |
7.0 MHz |
|
Capacitance L/L |
C |
≤0.6nF |
Capacitance L/PE |
C |
≤1.1nF |
Installation |
35mm DIN Rail |
|
Enclosure color |
Yellow or Gray |
|
Testing standard |
IEC 61643-21:2000 |