RS485 signal surge arrester 24Vdc
Item No: FS-DR-24/5.6
- Din rail signal surge arresters are applied to control signal double wire circuit in LPZ0 to LPZ3, e.g. 4~20mA circuit, RS485 circuit, RS422 circuit, gas detector, car-park system, CCTV remote monitor, remote control circuits.
- Common and difference surge protection mode, excellent performance.
- The pluggable module allows a fast replacement in case of fail.
- The grounding is realized through an earthing-clip on the DIN-Rail and / or earthing – clamp.
- No limiting in operating current due to parallel connecting method.
- Mounting on 35mm Rail, small space.
-Un 24Vdc, Uc 26.8Vdc
-Un 24Vdc, Uc 26.8Vdc
Product Description
1.Dimension and circuit diagram of RS485 signal surge arrester FS-DR-24/5.6
.jpg)
2.Electrical parameters of RS485 signal surge arrester FS-DR-24/5.6



.jpg)
2.Electrical parameters of RS485 signal surge arrester FS-DR-24/5.6
Rated voltage
|
Un
|
24 V
|
Max. cont. operating DC voltage
|
Uc
|
26.8 V
|
Max. cont. operating AC voltage
|
Uc
|
18.9 V
|
Rated current
|
1 A
|
|
Nominal discharge current (8/20μs)
|
In
|
5 kA
|
Max. discharge current (8/20μs)
|
Imax
|
10 kA
|
Voltage protection level L/L(limp D1)
|
Up
|
≤ 100 V
|
Voltage protection level L/PE (limp D1)
|
Up
|
≤ 80 V
|
Each line sereis resistance
|
1.8 Ohm
|
|
Band width L/L
|
5.6 MHz
|
|
Capacitance L/L
|
C
|
≤0.7nF
|
Capacitance L/PE
|
C
|
≤1.3nF
|
Installation
|
35mm DIN Rail
|
|
Enclosure color
|
Yellow or Gray
|
|
Testing standard
|
IEC 61643-21:2000
|