signal surge arrester DIN rail 10kA
Item No: FS-DR-60/10.0
- Din rail RS485 signal surge arresters are applied to control signal double wire circuit in LPZ0 to LPZ3, e.g. 4~20mA circuit, RS485 circuit, RS422 circuit, gas detector, car-park system, CCTV remote monitor, remote control circuits.
- Common and difference surge protection mode, excellent performance.
- The pluggable module allows a fast replacement in case of fail.
- The grounding is realized through an earthing-clip on the DIN-Rail and / or earthing – clamp.
- No limiting in operating current due to parallel connecting method.
- Mounting on 35mm Rail, small space.
-Un 60Vdc, Uc 70.1Vdc
-Un 60Vdc, Uc 70.1Vdc
Product Description
1.Dimension and circuit diagram of signal surge arrester FS-DR-60/10.0
2.Electrical parameters of signal surge arrester FS-DR-60/10.0
2.Electrical parameters of signal surge arrester FS-DR-60/10.0
Rated voltage
|
Un
|
60V
|
Max. cont. operating DC voltage
|
Uc dc
|
70.1 V
|
Max. cont. operating AC voltage
|
Uc ac
|
49.0V
|
Rated current
|
IL
|
500 mA
|
Nominal discharge current (8/20μs)
|
In
|
5 kA
|
Max. discharge current (8/20μs)
|
Imax
|
10 kA
|
Voltage protection level L/L(limp D1)
|
Up
|
≤ 240 V
|
Voltage protection levelL/PE (limp D1)
|
Up
|
≤ 150 V
|
Response time (L/L, L/PE)
|
tA
|
≤ 10ns
|
Each line sereis resistance
|
1.8 Ohm
|
|
Band width L/L
|
10.0MHz
|
|
Capacitance L/L
|
C
|
≤0.3nF
|
Capacitance L/PE
|
C
|
≤0.6nF
|
Installation
|
35mm DIN Rail
|
|
Enclosure color
|
Gray
|
|
Testingstandard
|
IEC 61643-21:2000
|