Loading Images

single phase 100kA MOV surge diverter

Item No: FB100B/1-275S

ØType 1 100kA@8/20μs single-phase lightning protection box.

ØEquipped with over temperature sound and light alarm indication and remote control contacts

ØUnique designing,Single Stage High Energy Handing Design Surge suppression module.

ØUsed in the lightning protection zones concept at boundary LPZ0B-LPZ1.

ØThe core component is an explosion-proof varistor with high discharge capacitance.

ØLow residual voltage.

ØProtection mode: L- N,N-PE

Product Description

1.Coding




2. Dimension 3. Circuit



4. Electrical parameters

Model. No.

FB100B/1-275S

SPD protection conforms to IEC61643-11 / EN61643-11

Type 1

SPD installation type conforms to IEC61643-11 / EN61643-11

ClassI

Protection level conforms to DIN VDE0675-6

B

Type of Network

TTTNIT

Protectionmode

L-N, N-PE

Nominal Voltage UN

220 Vac/50(60)Hz

Maximum continuous operating voltage UC

275 Vac/50(60)Hz

Continuous operating current IC

<50 µA

Residual current IPE

100 µA dc

500 µA ac

Standby power consumption PC

25 mVA

Nominal discharge current (8/20μs) In

50 kA

Maximum discharge current (8/20μs) Imax

100 kA

Impuse discharge current (10/350μs)N-PEIimp

50kA

Voltage protection level(Cat.C1 6kV 1.2/50μS 3KA 8/20μS) Up

<800V

Voltage protection level(Cat.C3 20kV 1.2/50μS 10KA 8/20μS) Up

<1500V

Voltage protection level (50KA 8/20μS) Up

≤3.3 kV

Isolation resistance Risol

100 MΩ

Response time tA

L-N

≤25 ns

N-PE

≤100 ns

Remote control contact

Volt free,5A 250VAC, NO/NC(option)

Display

One LED power indicator (green)

One LED failure indicator (blue or off)

Audible Alarm

Provided with shut-off SW

Test SW

Provided for testing internal operation main display and audible alarm function

Minimum area of connecting cable

10 mm2

Maximum area of connecting cable

25mm2

Installation location

Inside the cabinet

Module housing

Metal Housing

Shell spraying

Epoxy powder painter ventilated

Ambient temperature

0°C ~+60°C

Altitude

2000 m (amsl (above mean sea level))

Permissible humidity

30%~90%

5. Installation

Inquire