solar surge arrestor with LED display (150Vdc, Imax 4kA)
Item No: FV02D/2-150PV L
-Class III / Type3 solar surge arrestor with LED display.
-Visible fault indication - Green on: Normal; Green off: Fault.
-For using in the lightning protection zones concept at boundary 2-3.
-One-One correspondence reliable screening to ensure reliability.
-Lower voltage protection level Up.
-Visible fault indication - Green on: Normal; Green off: Fault.
-For using in the lightning protection zones concept at boundary 2-3.
-One-One correspondence reliable screening to ensure reliability.
-Lower voltage protection level Up.
Product Description
1.Dimension of DC surge protective device FV02D/2-150PV L
2.Electrical parameters of DC surge protective device FV02D/2-150PV L
3. Installation
2.Electrical parameters of DC surge protective device FV02D/2-150PV L
Test class according to IEC61643-1:2005
|
III
|
|
Max. Cont. Operating Voltage
|
Uc
|
150Vdc
|
Maximum discharge current (8/20μs)
|
Imax
|
4kA
|
Nominal discharge current (8/20μs)
|
In
|
2kA
|
Voltage protective level at In
|
Up
|
≤700V
|
Rated load current
|
IL
|
10A
|
Response time L-N, L(N)-PE
|
tA
|
≤25ns, ≤100ns
|
Conductor Recommended max.
|
2.5mm2
|
|
Mounting
|
35mmDin Rail
|
|
Operation temperature range
|
-40℃~+85℃
|
|
Degree of protection
|
IP20
|
|
Thermal Disconnector
|
Internal
|
|
Status Indicator
|
Green On:Normal;Green Off:Fault
|
|
Color
|
Gray
|
3. Installation