type 1+2 500Vdc surge protector
Item No: FV30B+C/2-500 PV S
-DC surge protector specially used for photovoltaic system 500Vdc.
-The core parts are metal oxide vristor components with high discharge capacity.
-With Reliable control thanks to Thermo Dynamic Control disconnector.
-Without remote signaling contact for control device.
-Fault indication via red mark in the inspection window.
- Type 1+2/ Class B+C
Product Description
1. Coding system
.png)
2. Type 1+2 500Vdc surge protector Dimension and Circuit



3. Type 1+2 500Vdc surge protector electrical parameters
4.Type 1+2 500Vdc surge protector installation
(1).jpg)
.png)
2. Type 1+2 500Vdc surge protector Dimension and Circuit



3. Type 1+2 500Vdc surge protector electrical parameters
Test class according to IEC61643-1:2005
|
I+II
|
||
Nominal Voltage
|
UN
|
500V DC
|
|
Max.continuous d.c. voltage[(L+/L-)->PE]/ [L+->L-]
|
Uc pv
|
560V DC
|
|
Maximum discharge current (8/20μs)
|
Imax
|
60kA
|
|
Nominal discharge current (8/20μs)
|
In
|
30kA
|
|
Impulse current (10/350μs)
|
Iimp
|
7kA
|
|
Voltage protective levelat In
|
Up
|
≤2.0kV
|
|
Isolation resistance
|
Risol
|
>102MΩ
|
|
Response time
|
tA
|
≤25ns
|
|
I/O Connections
|
By screw terminal:10-35mm2
By connection bus
|
||
Mounting
|
Symmetrical rail(EN50022/DIN46277-3)
|
||
Operation temperature range
|
-40℃~+85℃
|
||
Degree of protection
|
IP20
|
||
Housing material
|
UL94V0
|
||
Disconnection indicator
|
Mechanical indicator
|
||
Remote control contact
|
Without
|
||
Color
|
Gray
|
||
Isolation resistance
|
By screw terminal:10-35mm2
By connection bus
|
||
Response time
|
Symmetrical rail(EN50022/DIN46277-3)
|
4.Type 1+2 500Vdc surge protector installation
(1).jpg)