DIN rail Type 2 LED surge protection
2.Specifically for outdoor and commercial LED lighting applications, LED signage and traffic light manufacturers, including roadway lighting, parking garage lighting, wash wall lighting, traffic lighting, flood lighting, digital signage, street lightning, and tunneal lighting.
3.Imax 15kA lightning surge protection.
4.Varistor with built-in temperature tripping protection
5.Equipped with overload protection.Power supply disconnected when failure occurs
6.State indication
7.DIN rail installation
Product Description
2. .Circuit and dimension of DIN rail Type 2 LED surge protection
4. Electrical parameters of DIN rail Type 2 LED surge protection
Model. No. |
FLP05-275i-D |
|
SPD protection conforms to EN 61643-11 |
Type2+3 |
|
SPD installation type conforms to EN 61643-1 |
ClassII+III |
|
Protection level conforms to DIN VED 0675-6 |
C+D |
|
Type of Network |
LED light |
|
Protectionmode |
L-N , N-PE , L-PE |
|
Nominal Voltage 50(60)Hz UN |
230 V~ |
|
Maximum continuous operating voltage UC |
275 V~ |
|
Maximum discharge current (8/20μs) Imax |
15 kA |
|
Nominal discharge current (8/20μs) In |
5 kA |
|
Voltage protective level Up |
L-N |
≤1.3 kV |
N-PE |
≤0.5 kV |
|
L-PE |
≤1.5 kV |
|
Open circuit voltage Uoc |
10 kV |
|
Response time tA |
L-N |
≤25 ns |
N-PE |
≤100 ns |
|
Recommended back-up fuse |
20 AgL/gG |
|
Thermal Cut-off Member |
Internal |
|
Disconnection indicator |
LED indicator |
|
Degree of protection |
IP20 |
|
Mounting type |
35mm DIN rail acc. to EN 60715 |
|
Housing material |
UL94V-0 |
|
Ambient temperature |
-40°C ~+80°C |
|
Altitude |
≤2000m (amsl (above mean sea level)) |
|
Permissible humidity |
30%~90% |
5. Installation of DIN rail Type 2 LED surge protection